The R&S NGP800 DC power supply series, comprising five models with 400 W or 800 W, provides maximum power at a variety of operating points. The two or four 200 W outputs can each supply up to 64 V or up to 20 A. Electrically equivalent and galvanically isolated outputs can be wired in series or parallel for up to 250 V or 80 A.
Max. output power: 800 W
Max. voltage per channel: 32 V or 64 V
Max. current per channel: 10 A or 20 A
Up to 250 V or 80 A in series or parallel operation
Large touch display
Specifications
General
Product data applies under the following conditions:
► Three hours storage at ambient temperature followed by 30 minutes warm-up operation
► All data is valid at 23 °C (–3 °C/+7 °C) after 30 minutes warm-up time.
► Specified environmental conditions met
► Recommended calibration interval adhered to
► All internal automatic adjustments performed, if applicable
Specifications with limits
Represent warranted product performance by means of a range of values for the specified parameter. These specifications are marked with limiting symbols such as <, ≤, >, ≥, ±, or descriptions such as maximum, limit of, minimum. Compliance is ensured by testing or is derived from the design. Test limits are narrowed by guard bands to take into account measurement uncertainties, drift and aging, if applicable.
Specifications without limits
Represent warranted product performance for the specified parameter. These specifications are not specially marked and represent values with no or negligible deviations from the given value (for example, dimensions or resolution of a setting parameter). Compliance is ensured by design.
Measured values (meas.)
Characterize expected product performance by means of measurement results gained from individual samples.
Uncertainties
Represent limits of measurement uncertainty for a given measurand. Uncertainty is defined with a coverage factor of 2 and has been calculated in line with the rules of the Guide to the Expression of Uncertainty in Measurement (GUM), taking into account environmental conditions, aging, wear and tear.
Typical data as well as nominal and measured values are not warranted by Rohde & Schwarz.
In line with the 3GPP/3GPP2 standard, chip rates are specified in million chips per second (Mcps), whereas bit rates and symbol rates are specified in billion bits per second (Gbps), million bits per second (Mbps), thousand bits per second (kbps), million symbols per second (Msps) or thousand symbols per second (ksps), and sample rates are specified in million samples per second (Msample/s). Gbps, Mcps, Mbps, Msps, kbps, ksps and Msample/s are not SI units.
Available Models | ||||
Models | Number of output channels | Max. output power | Output voltage per channel | Output current per channel |
R&S®NGP802 | 2 | 400 W | 0 V to 32 V | 0 A to 20 A |
R&S®NGP804 | 4 | 800 W | 1 V to 32 V | 1 A to 20 A |
R&S®NGP814 | 4 | 800 W | Ch 1, Ch 2 0 V to 32 V | Ch 1, Ch 2 0 A to 20 A |
R&S®NGP822 | 2 | 400W | 0 V to 64 V | 0 A to 10 A |
R&S®NGP824 | 4 | 800 W | 0 V to 64 V | 0 A to 10 A |